APPLICATION:

Type MC Cable can be used to replace wire and conduit in applications such as cable tray, power lighting, service feeders and branch circuits as permitted by the National Electrical Code. KINGWIRE'S aluminum MC cable is suitable for use in concealed or exposed installations including environmental air spaces per NEC 300.22. In addition, KINGWIRE'S aluminum MC is suitable for use in vertical applications if installed per the NEC requirements of section 300-19 (a) and section 330.30.

PRODUCT FEATURES:

Type MC cable is constructed with 3 or 4 8000 series compact stranded aluminum XHHW-2 conductors cabled with a bare or insulated 8000 series aluminum grounding conductor. A binder identification baring tape is wrapped over the cabled assembly. Aluminum armor is interlocked over the conductor assembly. All insulated conductors are phase identified.

STANDARDS:

ULlogo1 

UL Standard 44, UL standard 1569, Federal Specification JC-30B,
ICEA S-66-524 and requirements of the National Electrical Code.
Compliant to RoHS, Directive 2002/95/EC, ICEA S-95-658, NEMA WC 70

 

 

KINGWIRE MC Cable

Cond. Size

AWG or

MCM

Sub Assembly

(O.D.)

Overall Diameter

(in)

Weight per 1000 ft. (lbs)

Ampacity

(amps)

75° C

Ampacity

(amps)

90° C

Three Conductor with Ground

6-6-6-6

0.57

0.78

237

50

55

4-4-4-6

0.66

0.88

298

65

75

2-2-2-6

0.78

1

411

90

100

1-1-1-4

0.89

1.11

496

100

115

1/0-1/0-1/0-4

0.97

1.19

578

120

135

2/0-2/0-2/0-4

1.06

1.27

678

135

150

3/0-3/0-3/0-4

1.16

1.38

833

155

175

4/0-4/0-4/0-2

1.27

1.59

1089

180

205

250-250-250-2

1.42

1.73

1275

205

230

300-300-300-2

1.51

1.79

1361

230

255

350-350-350-2

1.62

1.94

1653

250

280

400-400-400-1

1.72

2.04

1830

270

305

500-500-500-1

1.88

2.2

2177

310

350

600-600-600-1

2.1

2.4

2608

340

385

750-750-750-1/0

2.3

2.5

3118

385

435

 

Four Conductor with Ground

6-6-6-6-6

0.70

0.92

278

50

55

4-4-4-4-6

0.77

1.04

360

65

75

2-2-2-2-6

0.89

1.10

482

72

100

1-1-1-1-4

0.99

1.21

619

80

115

1/0-1/0-1/0-1/0-4

1.08

1.3

727

92

135

2/0-2/0-2/0-2/0-4

1.18

1.4

858

108

150

3/0-3/0-3/0-3/0-4

1.3

1.61

1138

124

175

4/0-4/0-4/0-4/0-2

1.42

1.74

1374

144

205

250-250-250-250-1

1.58

1.9

1634

184

230

300-300-300-300-1

1.70

1.99

1722

230

255

350-350-350-350-1/0

1.82

2.13

1969

250

280

400-400-400-400-1/0

1.91

2.20

2189

300

305

500-500-500-500-2/0

2.11

2.35

2653

310

350

600-600-600-600/2/0

2.35

2.67

3177

340

385

750-750-750-750/3/0

2.60

2.86

3858

385

435

Notes:
1. Ampacities shown are for general use as specified by the National Electrical Code, Section 310.15
Under normal conditions four conductor ampacities are not derated as shown above. If NEC Section 310.15 (b) (4) (a) does not consider the neutral as current carrying conductor, use ampacities listed for the three conductor cable.
2. Standard lengths are subject to normal manufacturing tolerance of +/- 10%
3. Other conductor sizes available upon request. Other ground sizes are available upon request.