800.453.5464

APPLICATION

Type USE-RHH-RHW-2 building wire and service cable is recognized for use as general purpose wiring at a maximum conductor temperature of 90°C in wet or dry locations for installation in air, conduit or other recognized raceways and for direct burial in circuits not exceeding 600 volts.

PRODUCT FEATURES

Compact stranded 8000 Series aluminum alloy conductor. Insulation is an abrasion, moisture, heat and sunlight resistant black cross-linked polyethylene (XLPE).

STANDARDS

KINGWIRE Type USE-RHH-RHW-2 conductors meet or exceed UL Standard 44 (RHW or RHH), UL Standard 854 (USE) and Federal Specification JC-30B NEC.

 

KINGWIRE USE-RHH-RHW-2

Conductor AWG or MCM

Stranding

Insulation Thickness (mils)

Outside Diameter (in)

Weight per 1000 ft. (lbs)

Ampacity (AMPS)

90°C

6

7/w

60

.290

49

60

4

7/w

60

.334

65

75

2

7/w

60

.390

94

100

1

19/w

80

.460

125

115

1/0

19/w

80

.500

150

135

2/0

19/w

80

.540

181

150

3/0

19/w

80

.590

220

175

4/0

19/w

80

.635

268

205

250

37/w

95

.710

320

230

350

37/w

95

.810

428

280

500

37/w

95

.930

591

350

600

61/w

110

1.035

715

385

750

61/w

110

1.130

873

435

1000

61/w

110

1.280

1132

500

1. Data are approximate and subject to normal manufacturing tolerances.
2. Standard lengths are subject to normal manufacturing tolerance of +/- 10%
3. Two, Three or four conductors can be paralleled on a reel.
4. 90°C-RHH dry locations, RHW-2 wet or dry locations.