600 VOLT
SECONDARY UD - DUPLEX

600 VOLT SECONDARY UD

APPLICATION

Directly buried or installed in ducts for 600 volt secondary distribution.

PRODUCT FEATURES

Concentric stranded or compressed 1350-H19 aluminum conductor, crosslinked polyethylene insulation. Insulated conductors surface printed, neutral, triple yellow striped or solid yellow. Black neutrals may be specified if desired.

STANDARDS

ULlogo1 

UL Standard 854 for Type USE-2, ASTM B-230, B-231 and
ICEA S-105-692, Federal Specification JC-30B NEC

 

KINGWIRE Duplex Conductor 600 Volt Secondary Type URD Cable - Aluminum Conductor

Code Word

Phase Conductors

Neutral Conductor

Single
Phase
Conductor
(in)

Outside
Diameter
(in)

Weight
per 1000 ft.
(lbs)

Ampacity

Size
AWG

Strand

Insulation Thickness
(MLS)

Size
AWG

Strand

Insulation Thickness
(MLS)

Direct Burial

In Duct

Bard

8

7/W

60

8

7/W

60

.262

.524

76

70

55

Clafin

6

7/W

60

6

7/W

60

.299

.596

91

95

70

Delgado

4

7/W

60

4

7/W

60

.345

.690

129

125

90

Everett

2

7/W

60

2

7/W

60

.403

.808

187

187

100

Ampacity: 90°C conductor temperature, 20°C ambient, RHO 90, 100% load factor for three conductor triplex with neutral carrying only unbalanced load.
All Yellow Extruded Stripe, cable is XLP insulation.
* To determine correct ampacity by conductor size, please consult the National Electric Code, latest edition.