600 VOLT
SECONDARY UD - DUPLEX
APPLICATION
Directly buried or installed in ducts for 600 volt secondary distribution.
PRODUCT FEATURES
Concentric stranded or compressed 1350-H19 aluminum conductor, crosslinked polyethylene insulation. Insulated conductors surface printed, neutral, triple yellow striped or solid yellow. Black neutrals may be specified if desired.
STANDARDS
UL Standard 854 for Type USE-2, ASTM B-230, B-231 and
ICEA S-105-692, Federal Specification JC-30B NEC
KINGWIRE Duplex Conductor 600 Volt Secondary Type URD Cable - Aluminum Conductor |
|||||||||||
Code Word |
Phase Conductors |
Neutral Conductor |
Single |
Outside |
Weight |
Ampacity |
|||||
Size |
Strand |
Insulation Thickness |
Size |
Strand |
Insulation Thickness |
Direct Burial |
In Duct |
||||
Bard |
8 |
7/W |
60 |
8 |
7/W |
60 |
.262 |
.524 |
76 |
70 |
55 |
Clafin |
6 |
7/W |
60 |
6 |
7/W |
60 |
.299 |
.596 |
91 |
95 |
70 |
Delgado |
4 |
7/W |
60 |
4 |
7/W |
60 |
.345 |
.690 |
129 |
125 |
90 |
Everett |
2 |
7/W |
60 |
2 |
7/W |
60 |
.403 |
.808 |
187 |
187 |
100 |
Ampacity: 90°C conductor temperature, 20°C ambient, RHO 90, 100% load factor for three conductor triplex with neutral carrying only unbalanced load.
All Yellow Extruded Stripe, cable is XLP insulation.
* To determine correct ampacity by conductor size, please consult the National Electric Code, latest edition.
The above data are approximate and subject to normal manufacturing tolerances.