SERVICE DROP
CABLE - DUPLEX
APPLICATION:
To supply 120 volts aerial service for temporary service at construction sites, outdoor or street lighting. For service at 600 volts or lower at conductor temperatures not to exceed 75°C for polyethylene insulated conductors or 90°C for crosslinked polyethylene (XLP) insulated conductors.
PRODUCT FEATURES:
Conductors are concentrically stranded, compressed 1350-H19 aluminum. Insulated with either polyethylene or XLP crosslinked polyethylene. Neutral messengers are concentrically stranded 6201, AAC or ACSR.
STANDARDS:
Service drop cable meets or exceeds the following ASTM specifications:
• B-230 Aluminum Wire, 1350-H19 for Electrical Purposes
• B-231 Aluminum Conductors, Concentric-Lay-Stranded
• B-232 Aluminum Conductors, Concentric-Lay-Stranded,
Coated Steel Reinforced (ACSR)
• B-399 Concentric-Lay-Stranded, 6201-T81 Aluminum Alloy Conductors
• B-901 Compressed Round Stranded Aluminum Conductors
Using Single Input Wire
• ANSI/ICEA S-76-474
KINGWIRE Duplex Service Drop - Aluminum Conductor AAC |
||||||||||
Code Word |
Phase Conductors |
Bare Neutral |
Weight per 1000 ft. (lbs) |
Rating (AMPS) |
||||||
Size AWG |
Strand |
Insulation Thickness (MLS) |
Size AWG |
Strand |
Breaking Strength (lbs) |
XLP |
Poly |
XLP |
Poly |
|
Peakingese |
6 |
Solid |
45 |
6 |
7/w |
563 |
63.5 |
61.7 |
85 |
70 |
Collie |
6 |
7/w |
45 |
6 |
7/w |
563 |
66.8 |
63.1 |
85 |
70 |
Dachshund |
4 |
Solid |
45 |
4 |
7/w |
881 |
95.5 |
93.4 |
110 |
90 |
Spaniel |
4 |
7/w |
45 |
4 |
7/w |
881 |
100.5 |
95.4 |
110 |
90 |
Doberman |
2 |
7/w |
45 |
2 |
7/w |
1,350 |
152.7 |
145.7 |
150 |
120 |
Malamute |
1/0 |
19/w |
60 |
1/0 |
7/w |
1,990 |
242.6 |
234.2 |
205 |
160 |
KINGWIRE Duplex Service Drop - Aluminum Conductor ACSR - Neutral Messenger |
||||||||||
Code Word |
Phase Conductors |
Bare Neutral |
Weight per 1000 (lbs) |
Rating (AMPS) |
||||||
Size AWG |
Strand |
Insulation Thickness (MLS) |
Size AWG |
Strand |
Breaking Strength (lbs) |
XLP |
Poly |
XLP |
Poly |
|
Setter |
6 |
Solid |
45 |
6 |
6/1 |
1,190 |
75.0 |
73.2 |
85 |
70 |
Shepherd |
6 |
7/w |
45 |
6 |
6/1 |
1,190 |
78.3 |
74.6 |
85 |
70 |
Eskimo |
4 |
Solid |
45 |
4 |
6/1 |
1,860 |
113.7 |
111.6 |
110 |
90 |
Terrier |
4 |
7/w |
45 |
4 |
6/1 |
1,860 |
118.7 |
113.6 |
110 |
90 |
Chow |
2 |
7/w |
45 |
2 |
6/1 |
2,850 |
181.7 |
174.7 |
150 |
120 |
Bull |
1/0 |
19/w |
60 |
1/0 |
6/1 |
4,380 |
288.7 |
280.3 |
200 |
160 |
KINGWIRE Duplex Service Drop - Aluminum Conductor AAAC - Alloy Neutral Messenger |
||||||||||
Code Word |
Phase Conductors |
Bare Neutral |
Weight per 1000 (lbs) |
Rating (AMPS) |
||||||
Size AWG |
Strand |
Insulation Thickness (MLS) |
Size AWG |
Strand |
Breaking Strength (lbs) |
XLP |
Poly |
XLP |
Poly |
|
Chihuahua |
6 |
Solid |
45 |
6 |
7/w |
1,110 |
67.6 |
65.8 |
85 |
70 |
Vizsla |
6 |
7/w |
45 |
6 |
7/w |
1,110 |
70.9 |
67.2 |
85 |
70 |
Harrier |
4 |
Solid |
45 |
4 |
7/w |
1,760 |
102.0 |
99.9 |
110 |
90 |
Whippet |
4 |
7/w |
45 |
4 |
7/w |
1,760 |
107.0 |
101.9 |
110 |
90 |
Schnauzer |
2 |
7/w |
45 |
2 |
7/w |
2,800 |
163.3 |
156.2 |
150 |
120 |
Heeler |
1/0 |
19/w |
60 |
1/0 |
7/w |
4,460 |
259.2 |
250.8 |
200 |
160 |
* Note: Designated sizes are ACSR 6/1 diameter equivalent resistivity per ASTM-B-399 for 6201. Conductor temperature of 90°C for XLP, 75°C for Poly; ambient temperatures of 40°C; emissivity 0.9; 2ft/sec. wind in sun.
** To determine current ampacity by conductor size, please consult The National Electric Code, latest edition.
The data is approximate and subject to normal manufacturing tolerances.