AL 2KV PV Wire
CONSTRUCTION PARAMETERS:
INSULATION: Flame retardant Cross-Linked Polyethylene (XLPE)
INSULATION COLOR: Black and Red
PHYSICAL PROPERTIES:
TEMPERATURE RANGE: -40°C to 90°C Dry, 90°C Wet. Rated for direct burial, moisture resistant, meets cold bend & cold impact test at -40°C
ELECTRICAL PROPERTIES
VOLTAGE RATING: 2,000 V for interconnection wiring of grounded and ungrounded photovoltaic power systems as described in Section 690.31 (A) and other applicable parts of the National Electrical Code (NEC), NFPA 70
STANDARDS:
UL 44 Type RHH/RHW-2, 2000V, UV/Sunlight Resistant
UL 854 Type USE-2
UL 4703 Type PV
ASTM B-800 , B-801
Flame Test: UL 1581 VW-1
IEEE383 for sizes 1/0 AWG and larger
ROHS, EPA 40 CFR, Part 26, Subpart C, heavy metals per Table 1, TLCP method
ASTM B836 COMPACT ROUNDED STRANDED ALUMINUM CONDUCTORS
KINGWIRE AL 2KV TYPE PV |
||||||
Conductor Size |
Conductor |
Nominal |
Min. Ave. Insulation |
Nominal |
Aluminum Weight (lbs/1000ft) |
Net Weight |
350 |
26/.1280 |
0.607 |
0.120 |
0.847 |
329 |
479 |
400 |
37/.1110 |
0.659 |
0.120 |
0.899 |
377 |
548 |
500 |
37/.1235 |
0.736 |
0.120 |
0.976 |
471 |
685 |
600 |
61/.1030 |
0.813 |
0.135 |
1.083 |
565 |
822 |
750 |
61/.1140 |
0.908 |
0.135 |
1.178 |
706 |
1027 |
Notes:
All dimensions and weights are subject to industry standards and tolerance unless otherwise noted.