SERVICE DROP
CABLE - QUADRUPLEX

600 VOLT SECONDARY UD - QUADRUPLEX

 

APPLICATION:

Used to supply 3 phase power, usually from a pole mounted transformer to the user’s service head where connection to the service entrance cable is made. To be used at voltages of 600 volts or less phase to phase and at conductor temperatures not to exceed 75°C for polyethylene insulated conductors or 90°C for crosslinked polyethylene (XLP) insulated conductors.

PRODUCT FEATURES:

Conductors are concentrically stranded, compressed 1350-H19 aluminum. Insulated with either polyethylene or XLP crosslinked polyethylene. Neutral messengers are concentrically stranded 6201, AAC or ACSR.

STANDARDS:

Service drop cable meets or exceeds the following ASTM specifications:

B-230 Aluminum Wire, 1350-H19 for Electrical Purposes

B-231 Aluminum Conductors, Concentric-Lay-Stranded

B-232 Aluminum Conductors, Concentric-Lay-Stranded,
   Coated Steel Reinforced (ACSR)

B-399 Concentric-Lay-Stranded, 6201-T81 Aluminum Alloy Conductors

B-901 Compressed Round Stranded Aluminum Conductors
   Using Single Input Wire

ANSI/ICEA S-76-474


 

 
 
 

KINGWIRE Quadruplex Service Drop - Aluminum Conductor AAC - Neutral Messenger

Code Word

Phase Conductors

Bare Neutral

Weight

per 1000 (lbs)

Rating

(AMPS)

Size

AWG

Strand

Insulation Thickness

(MLS)

Size

AWG

Strand

Breaking

Strength

(lbs)

XLP

Poly

XLP

Poly

Clydesdale

4

Solid

45

4

7

881

208

201

100

80

Pinto

4

7/w

45

4

7

881

223

207

100

80

Mustang

2

7/w

45

2

7

1,350

333

312

135

105

Criollo

1/0

19/w

60

1/0

7

1,990

529

504

180

135

Percheron

2/0

19/w

60

2/0

7

2,510

649

620

205

155

Hanovarian

3/0

19/w

60

3/0

19

3,310

799

765

235

180

Oldenburg

4/0

19/w

60

4/0

19

4,020

986

946

270

205

Lippizaner

336.4

19/w

60

336.4

19

6,146

1,546

1,519

330

240

KINGWIRE Quadruplex Service Drop - Aluminum Conductor ACSR- Neutral Messenger

Code Word

Phase Conductors

Bare Neutral

Weight

per 1000 (lbs)

Rating

(AMPS)

Size

AWG

Strand

Insulation Thickness

(MLS)

Size

AWG

Strand

Breaking

Strength

(lbs)

XLP

Poly

XLP

Poly

Morochuca

6

Solid

45

6

6/1

1,190

152

147

75

60

Chola

6

7/w

45

6

6/1

1,190

162

151

75

60

Morgan

4

Solid

45

4

6/1

1,860

226

220

100

80

Hackney

4

7/w

45

4

6/1

1,860

241

226

100

80

Palomino

2

7/w

45

2

6/1

2,850

362

342

135

105

Costena

1/0

19/w

60

1/0

6/1

4,380

575

550

180

135

Grullo

2/0

19/w

60

2/0

6/1

5,310

707

678

205

155

Suffolk

3/0

19/w

60

3/0

6/1

6,620

872

838

235

180

Appaloosa

4/0

19/w

60

4/0

6/1

8,350

1,079

1,039

270

205

Bronco

336.4

19/w

60

336.4

18/1

8,580

1,613

1,568

330

240

Gelding

336.4

19/w

60

4/0

6/1

8,350

1,548

1,494

330

240

KINGWIRE Quadruplex Service Drop - Aluminum Conductor AAAC-Alloy - Neutral Messenger

Code Word

Phase Conductors

Bare Neutral

Weight

per 1000 (lbs)

Rating

(AMPS)

Size

AWG

Strand

Insulation Thickness

(MLS)

Size

AWG

Strand

Breaking

Strength

(lbs)

XLP

Poly

XLP

Poly

Bay

6

Solid

45

6

7

1,110

145

140

75

60

French Coach

6

7/w

45

6

7

1,110

155

144

75

60

German Coach

4

Solid

45

4

7

1,760

214

208

100

80

Arabian

4

7/w

45

4

7

1,760

229

214

100

80

Belgian

2

7/w

45

2

7

2,800

344

323

135

105

Shetland

1/0

19/w

60

1/0

7

4,460

546

521

180

135

Thouroughbred

2/0

19/w

60

2/0

7

5,390

670

641

205

155

Trotter

3/0

19/w

60

3/0

7

6,790

825

791

235

180

Walking

4/0

19/w

60

4/0

7

8,560

1,019

979

270

205

* Note: Designated sizes are ACSR 6/1 diameter equivalent resistivity per ASTM-B-399 for 6201. Conductor temperature of 90°C for XLP, 75°C for Poly; ambient temperatures of 40°C; emissivity 0.9; 2ft/sec. wind in sun.
** To determine current ampacity by conductor size, please consult The National Electric Code, latest edition.