USE-RHH-RHW-2
APPLICATION:
Type USE-RHH-RHW-2 building wire and service cable is recognized for use as general purpose wiring at a maximum conductor temperature of 90°C in wet or dry locations for installation in air, conduit or other recognized raceways and for direct burial in circuits not exceeding 600 volts.
PRODUCT FEATURES:
Compact stranded 8000 Series aluminum alloy conductor. Insulation is an abrasion, moisture, heat and sunlight resistant black cross-linked polyethylene (XLPE).
STANDARDS:
UL Standard 44 (RHW or RHH), UL Standard 854 (USE) and
Federal Specification JC-30B NEC.
KINGWIRE USE-RHH-RHW-2 |
|||||
Conductor AWG or MCM |
Stranding |
Insulation Thickness (mils) |
Outside Diameter (in) |
Weight per 1000 ft. (lbs) |
Ampacity (AMPS) 90°C |
6 |
7/w |
60 |
.290 |
49 |
60 |
4 |
7/w |
60 |
.334 |
65 |
75 |
2 |
7/w |
60 |
.390 |
94 |
100 |
1 |
19/w |
80 |
.460 |
125 |
115 |
1/0 |
19/w |
80 |
.500 |
150 |
135 |
2/0 |
19/w |
80 |
.540 |
181 |
150 |
3/0 |
19/w |
80 |
.590 |
220 |
175 |
4/0 |
19/w |
80 |
.635 |
268 |
205 |
250 |
37/w |
95 |
.710 |
320 |
230 |
350 |
37/w |
95 |
.810 |
428 |
280 |
500 |
37/w |
95 |
.930 |
591 |
350 |
600 |
61/w |
110 |
1.035 |
715 |
385 |
750 |
61/w |
110 |
1.130 |
873 |
435 |
1000 |
61/w |
110 |
1.280 |
1132 |
500 |
1. Data are approximate and subject to normal manufacturing tolerances.
2. Standard lengths are subject to normal manufacturing tolerance of +/- 10%
3. Two, Three or four conductors can be paralleled on a reel.
4. 90°C-RHH dry locations, RHW-2 wet or dry locations.