APPLICATION:

Type USE-RHH-RHW-2 building wire and service cable is recognized for use as general purpose wiring at a maximum conductor temperature of 90°C in wet or dry locations for installation in air, conduit or other recognized raceways and for direct burial in circuits not exceeding 600 volts.

PRODUCT FEATURES:

Compact stranded 8000 Series aluminum alloy conductor. Insulation is an abrasion, moisture, heat and sunlight resistant black cross-linked polyethylene (XLPE).

STANDARDS:

ULlogo1 

UL Standard 44 (RHW or RHH), UL Standard 854 (USE) and
Federal Specification JC-30B NEC.

 

KINGWIRE USE-RHH-RHW-2

Conductor AWG or MCM

Stranding

Insulation Thickness (mils)

Outside Diameter (in)

Weight per 1000 ft. (lbs)

Ampacity (AMPS)

90°C

6

7/w

60

.290

49

60

4

7/w

60

.334

65

75

2

7/w

60

.390

94

100

1

19/w

80

.460

125

115

1/0

19/w

80

.500

150

135

2/0

19/w

80

.540

181

150

3/0

19/w

80

.590

220

175

4/0

19/w

80

.635

268

205

250

37/w

95

.710

320

230

350

37/w

95

.810

428

280

500

37/w

95

.930

591

350

600

61/w

110

1.035

715

385

750

61/w

110

1.130

873

435

1000

61/w

110

1.280

1132

500

1. Data are approximate and subject to normal manufacturing tolerances.
2. Standard lengths are subject to normal manufacturing tolerance of +/- 10%
3. Two, Three or four conductors can be paralleled on a reel.
4. 90°C-RHH dry locations, RHW-2 wet or dry locations.