BARE ALUMINUM AAC

AAC BARE ALUMINUM

AAC BARE ALUMINUM

APPLICATION

Stranded 1350 aluminum conductors shown in this section of data are classified as follows: Class AA for bare conductors usually used in overhead lines; Class A for conductors to be covered with weather-resistant materials and for bare conductors where greater flexibility is required.

Compact strand conductor for use in bare overhead applications or for use with weather-resistant coverings or insulations is also available.

Classes refer to stranding and are an indication of relative conductor flexibility, AA being the least flexible, C the most flexible.

 

PRODUCT FEATURES

Aluminum alloy 1350-H19 wires, concentrically stranded.

 

STANDARDS:

AAC bare conductors meet or excede the following ASTM Specifications:

  • B-230 Aluminum Wire, 1350-H19 for Electrical Purposes
  • B-231 Aluminum Conductors, Concentric-Lay-Stranded
  • B-400 Compact Round Concentric-Lay-Stranded Aluminum 1350 Conductors

SPECIFICATIONS

KINGWIRE AAC – BARE ALUMINUM

Code Word AWG Stranding Diameter Cross Sectional Area
(sq. in.)
Weight
per 1000 ft (Lbs)
Rated Breaking Strength (Lbs) Resistance OHMS/1000 ft Rating
(AMPS)
# of
Wires
Class Indiv. Wire Complete Cable OD DC
@ 20˚C
AC
@ 75˚C
Peachbell 6 7/w A .0612 .184 .0206 24.6 563 .658 .805 103
Rose 4 7/w A .0772 .232 .0328 39.2 881 .414 .506 138
Iris 2 7/w AA,A .0974 .292 .0521 62.3 1,350 .260 .318 185
Pansey 1 7/w AA,A .1093 .328 .0657 78.5 1,640 .207 .252 214
Poppy 1/0 7/w AA,A .1228 .368 .0829 99.1 1,990 .164 .202 247
Aster 2/0 7/w AA,A .1379 .414 .1045 124.9 2,510 .130 .159 286
Phlox 3/0 7/w AA,A .1548 .464 .1318 157.5 3,040 .103 .126 331
Oxlip 4/0 7/w AA,A .1739 .522 .1662 198.6 3,830 .0817 .0999 383
Sneezewort 250 7/w AA .1890 .567 .1964 234.7 4,520 .0691 .0846 425
Valerian 250 19/w A .1147 .574 .1964 234.7 4,660 .0691 .0846 426
Daisy 266.8 19/w AA .1953 .586 .2095 250.5 4,830 .0648 .0793 443
Laurel 266.8 19/w A .1185 .593 .2095 250.5 4,970 .0648 .0793 444
Peony 300 19/w A .1257 .629 .2356 286.1 5,480 .0576 .0706 478
Tulip 336.4 19/w A .1331 .666 .2642 315.8 6,150 .0514 .0630 513
Daffodil 350 19/w A .1357 .679 .2749 328.6 6,390 .0494 .0605 526
Canna 397.5 19/w AA,A .1447 .724 .3122 373.2 7,110 .0435 .0534 570
Goldentuft 450 19/w AA .1538 .769 .3534 422.4 7,890 .0384 .0472 616
Cosmos 477 19/w A .1584 .793 .3746 447.8 8,360 .0362 .0445 639
Syringa 477 37/w A .1135 .795 .3746 447.8 8,690 .0362 .0445 639
Zinnia 500 19/w AA .1622 .811 .3927 469.4 8,760 .0346 .0425 658
Hyacinth 500 37/w A .1162 .813 .329 469.4 9,110 .0346 .0425 658

KINGWIRE AAC – ALLOY BARE ALUMINUM

Code Word AWG Stranding Diameter Cross Sectional Area
(sq. in.)
Weight
per 1000 ft (Lbs)
Rated Breaking Strength (Lbs) Resistance OHMS/1000 ft Rating
(AMPS)
# of
Wires
Class Indiv. Wire Complete Cable OD DC
@ 20˚C
AC
@ 75˚C
Dahlia 556.5 19/w AA .1711 .856 .4371 522.4 9,750 .0311 .0382 703
Mistletoe 556.5 37/w AA,A .1226 .858 .4371 522.4 9,940 .0311 .0382 704
Meadowsweet 600 37/w AA,A .1273 .891 .4712 563.2 10,700 .0288 .0355 738
Orchid 636 37/w AA,A .1311 .918 .4995 597.0 11,400 .0272 .0355 765
Heuchera 650 37/w AA .1326 .928 .5105 610.2 11,600 .0266 .0328 775
Verbena 700 37/w AA .1375 .963 .5498 657.1 12,500 .0247 .0305 812
Flag 700 61/w A .1071 .964 .5498 657.1 12,900 .0274 .0305 812
Violet 715.5 37/w AA .1391 .974 .5620 671.7 12,800 .0242 .0299 823
Nasturtium 715.5 61/w A .1083 .975 .5620 671.7 13,100 .0242 .0299 823
Petunia 750 37/w AA .1424 .997 .5891 704.0 13,500 .0230 .0286 847
Cattail 750 61/w A .1109 .998 .5891 704.0 13,500 .0230 .0286 847
Arbutus 795 37/w AA .1446 1,026 .6244 746.3 13,900 .0217 .0271 878
Lilac 795 61/w A .1142 1,028 .6244 746.3 14,300 .0217 .0270 879
Cockscomb 900 37/w AA .1560 1,092 .7069 844.9 15,400 .0192 .0239 948
Snapdragon 900 61/w A .1215 1,094 .7069 844.9 15,900 .0192 .0239 948
Magnolia 954 37/w AA .1606 1,124 .7493 895.6 16,400 .0181 .0226 982
Goldenrod 954 61/w A .1251 1,126 .7493 895.6 16,900 .0181 .0226 983
Hawkweed 1000 37/w AA .1644 1,150 .7854 938.7 17,200 .0173 .0216 1010
Camellia 1000 61/w A .1280 1,152 .7854 938.7 17,700 .0173 .0216 1011
Bluebell 1033.5 37/w AA .1671 1,170 .8117 970.2 17,700 .0167 .0210 1031
Larkspur 1033.5 61/w A .1302 1,172 .8117 970.2 18,300 .0167 .0210 1032
Marigold 1113 61/w AA,A .1351 1,216 .8742 1045 19,700 .0155 .0195 1079
Hawthorn 1192.5 61/w AA,A .1398 1,258 .9366 1119 21,100 .0145 .0183 1124
Narcissus 1272 61/w AA,A .1444 1,300 .9990 1194 22,000 .0136 .0173 1169
Columbine 1351.5 61/w AA,A .1489 1,340 1,061 1269 23,400 .0128 .0163 1212
Carnation 1431 61/w AA,A .1532 1,379 1,124 1343 24,300 .0121 .0155 1253
Gladiolus 1510.5 61/w AA,A .1574 1,417 1,186 1418 25,600 .0144 .0147 1294
Coreopsis 1590 61/w AA .1614 1,454 1,249 1493 27,000 .0109 .0141 1333
Jessamine 1750 61/w AA .1694 1,525 1,374 1643 29,700 .00988 .0129 1408
Cowslip 2000 91/w A .1482 1,630 1,571 1877 34,200 .00864 .0115 1518
Sagebrush 2250 91/w A .1572 1,729 1,767 2131 37,500 .00776 .0105 1612
Lupine 2500 91/w A .1657 1,823 1,964 2370 41,900 .00698 .00969 1706
Bitterroot 2750 91/w A .1739 1,913 2,160 2607 46,100 .00635 .00900 1793
Trillium 3000 127/w A .1537 1,996 2,356 2844 50,300 .00582 .00834 1874
Bluebonnet 3500 127/w A .1660 2,158 2,749 3350 58,700 .0049 .00756 2024

1. Resistance is calculated using ASTM standard increments of stranding, and metal conductivies of 61.2% IACS for EC (1350), and 8% IACS for steel. AC (60 Hz) resistance includes current dependent hysteresis loss factor for 1 and 3 constructions.
2. Current ratings are based on 75°C conductor temperature, 25°C ambient, 2ft/sec wind, 96/watts/sq. foot sun, 0.5 coefficients of emissivity and absorption.

SPECIFICATIONS