SERVICE DROP DUPLEX

SERVICE DROP CABLE – DUPLEX

SERVICE DROP CABLE – DUPLEX

APPLICATION

To supply 120 volts aerial service for temporary service at construction sites, outdoor or street lighting. For service at 600 volts or lower at conductor temperatures not to exceed 75°C for polyethylene insulated conductors or 90°C for crosslinked polyethylene (XLP) insulated conductors.

 

PRODUCT FEATURES

Conductors are concentrically stranded, compressed 1350-H19 aluminum. Insulated with either polyethylene or XLP crosslinked polyethylene. Neutral messengers are concentrically stranded 6201, AAC or ACSR.

 

STANDARDS:

Service drop cable meets or exceeds the following ASTM specifications:

  • B-230 Aluminum Wire, 1350-H19 for Electrical Purposes
  • B-231 Aluminum Conductors, Concentric-Lay-Stranded
  • B-232 Aluminum Conductors, Concentric-Lay-Stranded, Coated Steel Reinforced (ACSR)
  • B-399 Concentric-Lay-Stranded, 6201-T81 Aluminum Alloy Conductors
  • B-901 Compressed Round Stranded Aluminum Conductors Using Single Input Wire
  • ANSI/ICEA S-76-474

SPECIFICATIONS

KINGWIRE DUPLEX SERVICE DROP – ALUMINUM CONDUCTOR AAC

Code Word Phase Conductors Bare Neutral Weight
per 1000 ft.
(lbs)
Rating (AMPS)
Size
AWG
Strand Insulation Thickness
(MLS)
Size
AWG
Strand Breaking Strength (lbs) XLP Poly XLP Poly
Peakingese 6 Solid 45 6 7/w 563 63.5 61.7 85 70
Collie 6 7/w 45 6 7/w 563 66.8 63.1 85 70
Dachshund 4 Solid 45 4 7/w 881 95.5 93.4 110 90
Spaniel 4 7/w 45 4 7/w 881 100.5 95.4 110 90
Doberman 2 7/w 45 2 7/w 1,350 152.7 145.7 150 120
Malamute 1/0 19/w 60 1/0 7/w 1,990 242.6 234.2 205 160

KINGWIRE DUPLEX SERVICE DROP – ALUMINUM CONDUCTOR ACSR – NEUTRAL MESSENGER

Code Word Phase Conductors Bare Neutral Weight
per 1000 ft.
(lbs)
Rating (AMPS)
Size
AWG
Strand Insulation Thickness
(MLS)
Size
AWG
Strand Breaking Strength (lbs) XLP Poly XLP Poly
Setter 6 Solid 45 6 6/1 1,190 75.0 73.2 85 70
Shepherd 6 7/w 45 6 6/1 1,190 78.3 74.6 85 70
Eskimo 4 Solid 45 4 6/1 1,860 113.7 111.6 110 90
Terrier 4 7/w 45 4 6/1 1,860 118.7 113.6 110 90
Chow 2 7/w 45 2 6/1 2,850 181.7 174.7 150 120
Bull 1/0 19/w 60 1/0 6/1 4,380 288.7 280.3 200 160

KINGWIRE DUPLEX SERVICE DROP – ALUMINUM CONDUCTOR AAAC – ALLOY NEUTRAL MESSENGER

Code Word Phase Conductors Bare Neutral Weight
per 1000 ft.
(lbs)
Rating (AMPS)
Size
AWG
Strand Insulation Thickness
(MLS)
Size
AWG
Strand Breaking Strength (lbs) XLP Poly XLP Poly
Chihuahua 6 Solid 45 6 7/w 1,110 67.6 65.8 85 70
Vizsla 6 7/w 45 6 7/w 1,110 70.9 67.2 85 70
Harrier 4 Solid 45 4 7/w 1,760 102.0 99.9 110 90
Whippet 4 7/w 45 4 7/w 1,760 107.0 101.9 110 90
Schnauzer 2 7/w 45 2 7/w 2,800 163.3 156.2 150 120
Heeler 1/0 19/w 60 1/0 7/w 4,460 259.2 250.8 200 160

* Note: Designated sizes are ACSR 6/1 diameter equivalent resistivity per ASTM-B-399 for 6201. Conductor temperature of 90°C for XLP, 75°C for Poly; ambient temperatures of 40°C; emissivity 0.9; 2ft/sec. wind in sun.
** To determine current ampacity by conductor size, please consult The National Electric Code, latest edition.
The data is approximate and subject to normal manufacturing tolerances.