SERVICE DROP QUADRUPLEX

SERVICE DROP CABLE – QUADRUPLEX

SERVICE DROP CABLE – QUADRUPLEX

APPLICATION

Used to supply 3 phase power, usually from a pole mounted transformer to the user’s service head where connection to the service entrance cable is made. To be used at voltages of 600 volts or less phase to phase and at conductor temperatures not to exceed 75°C for polyethylene insulated conductors or 90°C for crosslinked polyethylene (XLP) insulated conductors.

 

PRODUCT FEATURES

Conductors are concentrically stranded, compressed 1350-H19 aluminum. Insulated with either polyethylene or XLP crosslinked polyethylene. Neutral messengers are concentrically stranded 6201, AAC or ACSR.

 

STANDARDS:

Service drop cable meets or exceeds the following ASTM specifications:

  • B-230 Aluminum Wire, 1350-H19 for Electrical Purposes
  • B-231 Aluminum Conductors, Concentric-Lay-Stranded
  • B-232 Aluminum Conductors, Concentric-Lay-Stranded, Coated Steel Reinforced (ACSR)
  • B-399 Concentric-Lay-Stranded, 6201-T81 Aluminum Alloy Conductors
  • B-901 Compressed Round Stranded Aluminum Conductors Using Single Input Wire
  • ANSI/ICEA S-76-474

SPECIFICATIONS

KINGWIRE QUADRUPLEX SERVICE DROP – ALUMINUM CONDUCTOR AAC – NEUTRAL MESSENGER

Code Word Phase Conductors Bare Neutral Weight
per 1000 ft.
(lbs)
Rating (AMPS)
Size
AWG
Strand Insulation Thickness
(MLS)
Size
AWG
Strand Breaking Strength (lbs) XLP Poly XLP Poly
Clydesdale 4 Solid 45 4 7 881 208 201 100 80
Pinto 4 7/w 45 4 7 881 223 207 100 80
Mustang 2 7/w 45 2 7 1,350 333 312 135 105
Criollo 1/0 19/w 60 1/0 7 1,990 529 504 180 135
Percheron 2/0 19/w 60 2/0 7 2,510 649 620 205 155
Hanovarian 3/0 19/w 60 3/0 19 3,310 799 765 235 180
Oldenburg 4/0 19/w 60 4/0 19 4,020 986 946 270 205
Lippizaner 336.4 19/w 60 336.4 19 6,146 1,546 1,519 330 240

KINGWIRE QUADRUPLEX SERVICE DROP – ALUMINUM CONDUCTOR ACSR- NEUTRAL MESSENGER

Code Word Phase Conductors Bare Neutral Weight
per 1000 ft.
(lbs)
Rating (AMPS)
Size
AWG
Strand Insulation Thickness
(MLS)
Size
AWG
Strand Breaking Strength (lbs) XLP Poly XLP Poly
Morochuca 6 Solid 45 6 6/1 1,190 152 147 75 60
Chola 6 7/w 45 6 6/1 1,190 162 151 75 60
Morgan 4 Solid 45 4 6/1 1,860 226 220 100 80
Hackney 4 7/w 45 4 6/1 1,860 241 226 100 80
Palomino 2 7/w 45 2 6/1 2,850 362 342 135 105
Costena 1/0 19/w 60 1/0 6/1 4,380 575 550 180 135
Grullo 2/0 19/w 60 2/0 6/1 5,310 707 678 205 155
Suffolk 3/0 19/w 60 3/0 6/1 6,620 872 838 235 180
Appaloosa 4/0 19/w 60 4/0 6/1 8,350 1,079 1,039 270 205
Bronco 336.4 19/w 60 336.4 18/1 8,580 1,613 1,568 330 240
Gelding 336.4 19/w 60 4/0 6/1 8,350 1,548 1,494 330 240

KINGWIRE QUADRUPLEX SERVICE DROP – ALUMINUM CONDUCTOR AAAC-ALLOY – NEUTRAL MESSENGER

Code Word Phase Conductors Bare Neutral Weight
per 1000 ft.
(lbs)
Rating (AMPS)
Size
AWG
Strand Insulation Thickness
(MLS)
Size
AWG
Strand Breaking Strength (lbs) XLP Poly XLP Poly
Bay 6 Solid 45 6 7 1,110 145 140 75 60
French Coach 6 7/w 45 6 7 1,110 155 144 75 60
German Coach 4 Solid 45 4 7 1,760 214 208 100 80
Arabian 4 7/w 45 4 7 1,760 229 214 100 80
Belgian 2 7/w 45 2 7 2,800 344 323 135 105
Shetland 1/0 19/w 60 1/0 7 4,460 546 521 180 135
Thouroughbred 2/0 19/w 60 2/0 7 5,390 670 641 205 155
Trotter 3/0 19/w 60 3/0 7 6,790 825 791 235 180
Walking 4/0 19/w 60 4/0 7 8,560 1,019 979 270 205

* Note: Designated sizes are ACSR 6/1 diameter equivalent resistivity per ASTM-B-399 for 6201. Conductor temperature of 90°C for XLP, 75°C for Poly; ambient temperatures of 40°C; emissivity 0.9; 2ft/sec. wind in sun.
** To determine current ampacity by conductor size, please consult The National Electric Code, latest edition.
The data is approximate and subject to normal manufacturing tolerances.

SPECIFICATIONS