USE-RHH-RHW-2

USE-2/RHH/RHW-2

USE-2/RHH/RHW-2

APPLICATION:

Type USE-2 or RHH/RHW-2 building wire and service cable is recognized for use as general purpose wiring at a maximum conductor temperature of 90°C in wet or dry locations for installation in air, conduit or other recognized raceways and for direct burial in circuits not exceeding 600 volts.

 

PRODUCT FEATURES:

Compact stranded 8000 Series aluminum alloy conductor.
Insulation is an abrasion, moisture, heat and sunlight resistant black cross-linked polyethylene (XLPE).

 

STANDARDS:

UL 44 (RHH/RHW-2)
UL 854 (USE-2)
ASTM B800, B801
Federal Specification A-A59544 (formerly J-C-30B)
Compliant to RoHS (Directive 2011/65/EU)

SPECIFICATIONS

KINGWIRE USE-2 or RHH/RHW-2     Physical Characteristics

Conductor Size Stranding Conductor Nominal Diameter Insulation
Thickness
Nominal Outside
Diameter
AL
Weight
Nominal Cable Weight Maximum Pulling Tension Minimum Bending Radius*
AWG/Kcmil Min. No. inch mils inch lb/1000ft lb/1000ft lb inch
6 7 0.169 60 0.292 25 46 157 1.2
4 7 0.213 60 0.336 39 64 250 1.3
2 7 0.268 60 0.391 63 93 398 1.6
1 18 0.299 80 0.462 79 125 502 1.8
1/0 18 0.336 80 0.499 99 149 634 2.0
2/0 18 0.376 80 0.539 125 180 799 2.2
3/0 18 0.423 80 0.586 158 218 1007 2.3
4/0 18 0.475 80 0.638 199 266 1270 2.6
250 35 0.520 95 0.715 235 324 1500 2.9
350 35 0.616 95 0.811 329 431 2100 3.2
500 35 0.736 95 0.931 471 591 3000 3.7
600 58 0.813 110 1.038 565 718 3600 5.2
750 58 0.908 110 1.133 706 875 4500 5.7
1000 58 1.060 110 1.285 941 1135 6000 6.4

1. Data are approximate and subject to normal manufacturing tolerances.
2. Standard lengths are subject to normal manufacturing tolerance of +/- 10%
3. Two, Three or Four conductors can be paralleled on a reel.
4. 90°C-RHH dry locations, RHW-2 wet or dry locations.
* Minimum bending radius shown applies to permanent installation. Larger radius should be used during cable pulling.

KINGWIRE USE-2 or RHH/RHW-2     Electrical Characteristics

Conductor Size DC Resistance
@ 25°C
AC Resistance
@ 75°C
Inductive Reactance+ Ampacity
@ 75°C*
Ampacity
@ 90°C*
AWG/Kcmil Ω/1000ft Ω/1000ft Ω/1000ft amps amps
6 0.674 0.82 0.051 50 55
4 0.424 0.51 0.048 65 75
2 0.267 0.32 0.045 90 100
1 0.211 0.26 0.046 100 115
1/0 0.168 0.20 0.044 120 135
2/0 0.133 0.16 0.043 135 150
3/0 0.105 0.13 0.042 155 175
4/0 0.084 0.10 0.041 180 205
250 0.071 0.086 0.041 205 230
350 0.051 0.062 0.040 250 280
500 0.035 0.044 0.039 310 350
600 0.029 0.036 0.039 340 385
750 0.024 0.031 0.038 385 435
1000 0.018 0.025 0.037 445 500

*Ampacities are based on NEC 2023 Table 310.16, Ampacities of Insulated Conductors in Raceway, Cable, or Earth (Directly Buried). Not more than 3 current-carrying conductors. Ambient temperature of 30°C.
+Inductive reactance based on NEC 2023 Table 9, 600-Volt Cables, 3-Phase, 60 Hz, 75°C, 3-1/C in non-ferrous conduit.