SERVICE DROP TRIPLEX

SERVICE DROP CABLE – TRIPLEX

SERVICE DROP CABLE – TRIPLEX

APPLICATION

To supply power from the utility’s lines to the consumer’s weatherhead. For service at 600 volts or less (phase to phase) at a conductor temperature of 75°C maximum for polyethylene insulation or 90°C maximum for crosslinked polyethylene (XLP) insulated conductors.

 

PRODUCT FEATURES

Conductors are concentrically stranded, compressed 1350-H19 aluminum. Insulated with either polyethylene or XLP crosslinked polyethylene. Neutral messengers are concentrically stranded 6201, AAC or ACSR.

 

STANDARDS:

Service drop cable meets or exceeds the following ASTM specifications:

  • B-230 Aluminum Wire, 1350-H19 for Electrical Purposes
  • B-231 Aluminum Conductors, Concentric-Lay-Stranded
  • B-232 Aluminum Conductors, Concentric-Lay-Stranded,
    Coated Steel Reinforced (ACSR)
  • B-399 Concentric-Lay-Stranded, 6201-T81 Aluminum Alloy Conductors
  • B-901 Compressed Round Stranded Aluminum Conductors Using Single Input Wire
  • ANSI/ICEA S-76-474

SPECIFICATIONS

KINGWIRE TRIPLEX SERVICE DROP – AAAC-ALLOY NEUTRAL MESSENGER

Code Word Phase Conductors Bare Neutral Weight
per 1000 ft.
(lbs)
Rating (AMPS)
Size
AWG
Strand Insulation Thickness
(MLS)
Size
AWG
Strand Breaking Strength (lbs) XLP Poly XLP Poly
Minex 6 Solid 45 6 7 1,110 106.6 102.9 85 70
Hippa 6 7/w 45 6 7 1,110 107.0 105.7 85 70
Prawn 4 Solid 45 4 7 1,760 158.4 154.1 110 90
Barnacles 4 7/w 45 4 7 1,760 160.0 157.0 110 90
Shrimp 2 7/w 45 2 7 2,800 243.0 238.0 150 115
Gammarus 1/0 7/w 60 1/0 7 4,460 390.0 384.0 200 155
Leda 1/0 19/w 60 1/0 7 4,460 384.0 378.0 200 155
Dungenese 2/0 7/w 60 2/0 7 5,390 481.0 474.0 230 180
Cyclops 2/0 19/w 60 2/0 7 5,390 473.0 467.0 230 180
Flustra 3/0 19/w 60 3/0 7 6,790 596.0 589.1 260 205
Lepas 4/0 19/w 60 4/0 7 8,560 725.0 716.0 300 235

KINGWIRE TRIPLEX SERVICE DROP – ALUMINUM CONDUCTOR – AAAC – ALLOY REDUCED NEUTRAL MESSENGER

Code Word Phase Conductors Bare Neutral Weight
per 1000 ft.
(lbs)
Rating (AMPS)
Size
AWG
Strand Insulation Thickness
(MLS)
Size
AWG
Strand Breaking Strength (lbs) XLP Poly XLP Poly
Artemia 4 Solid 45 6 7 1,110 134.0 132.0 110 90
Crab 4 7/w 45 6 7 1,110 144.0 141.2 110 90
Solaster 2 7/w 45 4 7 1,760 216.0 212.6 150 115
Sandcrab 1/0 7/w 60 2 7 2,800 348.0 341.0 200 155
Echinus 1/0 19/w 60 2 7 2,800 342.0 336.0 200 155
Crayfish 2/0 7/w 60 1 7 3,530 452.6 422.5 230 180
Sipho 2/0 19/w 60 1 7 3,530 441.0 422.5 230 180
Fulgar 3/0 19/w 60 1/0 7 4,460 525.0 518.0 260 205
Arca 4/0 19/w 60 2/0 7 5,360 640.0 632.0 300 235

KINGWIRE TRIPLEX SERVICE DROP – ALUMINUM CONDUCTOR – AAC – NEUTRAL MESSENGER

Code Word Phase Conductors Bare Neutral Weight
per 1000 ft.
(lbs)
Rating (AMPS)
Size
AWG
Strand Insulation Thickness
(MLS)
Size
AWG
Strand Breaking Strength (lbs) XLP Poly XLP Poly
Haiotis 6 Solid 45 6 7 563 102.5 98.8 85 70
Patella 6 7/w 45 6 7 563 104.0 101.6 85 70
Fusus 4 Solid 45 4 7 881 151.9 147.6 110 90
Oyster 4 7/w 45 4 7 881 154.0 151.7 110 90
Clam 2 7/w 45 2 7 1,350 232.0 228.0 150 115
Murex 1/0 7/w 1/0 1/0 7 1,990 374.0 367.0 200 155
Purpura 1/0 19/w 1/0 1/0 7 1,990 368.0 362.0 200 155
Nassa 2/0 7/w 2/0 2/0 7 2,510 461.0 453.0 230 180
Melita 3/0 19/w 3/0 3/0 19 3,310 585.2 562.9 260 205
Portunus 4/0 19/w 4/0 4/0 19 4,020 693.0 684.0 300 235
Nannynose 336.4 19/w 336.4 336.4 19 6,146 1,111.0 1,096.0 380 290

KINGWIRE TRIPLEX SERVICE DROP – ALUMINUM CONDUCTOR – FULL SIZE ACSR MESSENGER

Code Word Phase Conductors Bare Neutral Weight
per 1000 ft.
(lbs)
Rating (AMPS)
Size
AWG
Strand Insulation Thickness
(MLS)
Size
AWG
Strand Breaking Strength (lbs) XLP Poly XLP Poly
Paludina 6 Solid 45 6 6/1 1,190 114 113 85 70
Voluta 6 7/w 45 6 6/1 1,190 115 112 85 70
Whelk 4 Solid 45 4 6/1 1,860 163 161 110 90
Periwinkle 4 7/w 45 4 6/1 1,860 172 169 110 90
Conch 2 7/w 45 2 6/1 2,850 262 257 150 115
Neritina 1/0 7/w 60 1/0 6/1 4,380 420 414 200 115
Cenia 1/0 19/w 60 1/0 6/1 4,380 414 408 200 115
Runcina 2/0 7/w 60 2/0 6/1 5,310 519 512 230 180
Triton 2/0 19/w 60 2/0 6/1 5,310 511 505 230 180
Cherrystone 3/0 7/w 60 3/0 6/1 6,620 656 643 260 205
Mursia 3/0 19/w 60 3/0 6/1 6,620 633 626 260 205
Razor 4/0 7/w 60 4/0 6/1 8,350 814 799 300 235
Zuzara 4/0 19/w 60 4/0 6/1 8,350 785 777 300 235
Limpet 336.4 19/w 80 336.4 18/1 8,680 1,160 1,147 300 290

KINGWIRE TRIPLEX SERVICE DROP – ALUMINUM CONDUCTOR – ACSR REDUCED SIZE MESSENGER

Code Word Phase Conductors Bare Neutral Weight
per 1000 ft.
(lbs)
Rating (AMPS)
Size
AWG
Strand Insulation Thickness
(MLS)
Size
AWG
Strand Breaking Strength (lbs) XLP Poly XLP Poly
Scallop 4 Solid 45 6 6/1 1,190 142 139 110 90
Strombus 4 7/w 45 6 6/1 1,190 151 148 110 90
Cockle 2 7/w 45 4 6/1 1,860 228 224 150 115
Janthina 1/0 7/w 60 2 6/1 2,850 367 360 200 155
Ranella 1/0 19/w 60 2 6/1 2,850 361 356 200 155
Cavolinia 2/0 7/w 60 1 6/1 3,550 452 444 230 180
Clio 2/0 19/w 60 1 6/1 3,550 444 437 230 180
Sanddollar 3/0 7/w 60 1/0 6/1 4,380 570 557 260 205
Aega 3/0 19/w 60 1/0 6/1 4,380 565 552 260 205
Cutlefish 4/0 7/w 60 2/0 6/1 5,310 706 691 300 235
Cerapus 4/0 19/w 60 2/0 6/1 5,310 678 670 300 235
Cowry 336.4 19/w 80 4/0 6/1 8,350 1,135 1,093 380 290

* Note: Designated sizes are ACSR 6/1 diameter equivalent resistivity per ASTM-B-399 for 6201. Conductor temperature of 90°C for XLP, 75°C for Poly; ambient temperatures of 40°C; emissivity 0.9; 2ft/sec. wind in sun.
** To determine current ampacity by conductor size, please consult The National Electric Code, latest edition.
The data is approximate and subject to normal manufacturing tolerances.