SEU

TYPE SE STYLE (U)

TYPE SE STYLE (U)

APPLICATION:

KINGWIRE Service Entrance Cable Style U (SEU) is for use as primary cable to deliver overhead electrical service from the service head to house meter, 90°C wet or dry and interior wiring applications. The voltage rating is 600V.

 

PRODUCT FEATURES:

  • KINGWIRE Type SE cable is constructed with AA-8000 series aluminum alloy, compact stranded conductors.
  • Cross-linked polyethylene insulation rated for a maximum operation temperature of 90°C in wet and dry locations.
  • Eco friendly sunlight resistant, flame retardant and heavy metal free Polyvinyl Chloride (PVC) Jacket.
  • Insulation and Jacket materials are in compliance with RoHS, Directive 2002/95/EC.
  • Sequential foot markings for easier inventory control management.

 

STANDARDS:

UL Standard 44 for type XHHW-2 conductors, (UL) Standard 854, Federal Specification JC-30B NEC, Approved for use in accordance with the requirements of the NEC NFPA 70, 2011 Edition.

SPECIFICATIONS

KINGWIRE Service Entrance Cable Style U (SEU)

Size AWG & Construction Stranding Outside Diameter (in) Weight per
1000 ft. (lbs)
Ampacity (AMPS) *
Phase
Conductors
Bare Ground 90˚ C Dwelling
6-6-6 7 11 .458 x .720 143 60
4-4-4 7 16 .505 x .811 198 75
4-4-6 7 11 .502 x 808 184 75
2-2-2 7 15 .559 x .919 282 100 100
2-2-4 7 16 .559 x .919 259 100 100
1/0-1/0-1/0 19 18 .661 x 1.095 438 135 125
1/0-1/0-2 19 14 .647 x 1.095 387 135 125
2/0-2/0-2/0 19 18 .719 x 1.208 516 150 150
2/0-2/0-1 19 14 .702 x 1.190 467 150 150
4/0-4/0-4/0 19 30 .857 x 1.445 770 205 200
4/0-4/0-2/0 19 18 .818 x 1.406 692 205 200

Notes: Data are approximate and subject to normal manufacturing tolerances.
* To determine correct ampacity by conductor size, please consult the National Electric Code, latest edition.

SPECIFICATIONS

Hi, How Can We Help You?